Reed Switch Protection
Point Level Switch
Our custom level switches operate on the principal of a magnet-equipped float, or
floats, activating a reed switch (float station) at customer requested dimensions and
state (N/O or N/C dry). The custom sizing combined with low activation energy reed
switches sealed in their own hermetic environment allow our controls to handle huge
jobs from small places - any job as long as the capacity is not exceeded. Make sure
there is enough capacity - if not, simply use an accessory interface device, such as a
relay, to handle the required load. In other words, let the switch sense and the relay or
electronics control. Only test with an Ohm meter not a light. Level switches are really
for pilot duty devices and will work well with a control relay.
The Reed Switch
The tiny switches are comprised of a sealed glass tube containing spring arms with
rhodium contact material. The magnets close the contacts when they are within the
required range. Like a computer chip –its small size does not limit it to small jobs. It can
do big jobs from restricted spaces as long as the capacity is not exceeded.
Possible Problems
Two common causes can destroy the switch. First - if the power rating of the switch is
greatly exceeded, the contacts will weld immediately. Second - if the switch is induced
to arc as it opens or closes the plated contact surface will fail. The greater the arc - the
sooner the failure. The switch will weld in the closed position. Switches are rated with a
resistive load - ARC suppression is important.
How to Suppress the Arc (RELAY)
For a DC circuit - a simple one-amp diode placed parallel with the load will suppress
the arc. Select a diode with a voltage rating at least three times or more that of your
circuit rating. Connect cathode to positive. Cathode usually has a dark ring, on the
body, on the same side. e.g. 1N4004 For an AC circuit use a disk capacitor / resistor
placed parallel with the switch. Select a 0.1 mfd 400 to 600 V capacitor. Place a 50 -
100-ohm 1/4-watt resistor in series with the capacitor. Place the pieces parallel to the
switch. (A Varistor V130LA10A will also work in AC)
Interface or Control Devices
Solid State:
SCR’s or Triacs are an effective off the shelf product for controlling alarm lights or
latching or holding relays. Latching relays would be used for high/low level control. The
switch only sees a milliamp resistive signal load from the solid-state device. Most solidstate
devices c/w arc suppression if needed. Solid state devices are readily available at
most electronic outlets or from your level switch distributor.
Electromechanical Relays
A great simple device and can be wired in any conceivable logic. A suppression circuit
as above should
be used with mechanical relays as the reed switch would see an inductive load.
Other Devices
Thousands of control devices are available such as the 5-volt non-arcing computer brain. The new world is controlled by low voltage computer chips where power levels are low - an ideal situation for our level switches. Let the switches control for example LED’s, computer outputs, solid-state devices and small indicator lamps. Use an interface to control motor starters, motors, lamps or heating devices, etc.
Reed Switch
Maximum voltage SPST: 200 VDC / 240 VAC
Maximum voltage SPDT: 150 VDC / VAC
Maximum amps switching: 0.5 amps
Max Power SPST: 70 Watt
Max Power SPDT: 20 Watt
Hermetically sealed
Quality
Over thirty years worth of our level switches are in use around the world. They can be found in a multitude of level applications. Many OEM’s from our early days are still with us.
IMPORTANT INFORMATION ON USE
Single Point Level Switch Including Side Mount
Best used as an alarm signal they have a narrow differential between off and on. Unless they are controlled by a time delay or other such logic they will cycle rapidly and cause premature failure. Wave
action could have the same effect on the switch. A slosh control device would help.
Multi Point Level Switches Including Bent Stem
Can be used for level control with up to 6 stations for alarms and level control. Use an appropriate control
device.
Fail Safe Installation
Always design the system for fail-safe operation - an example would be - liquids should not overflow because of a power failure. Failure of a relay or pump should not allow the liquid to overflow. Also –failure of a level switch should not cause conditions to be unsafe. Level controls should be satisfied by intelligent fail-safe design. A back-up design or setup should be incorporated if a fail-safe design cannot be achieved by circuit and or component configuration. It is important and the responsibility of the purchasing Engineer, who delegates control of a design to automate, to insure a means to sustain safe control when components or power fails.
Will it do Your Job?
The controls are built to customer requests. The company does not recommend products for any specific use. We will discuss design and details with user engineers. All components are assembled from part numbers described in the brochure. The company, as described in the warranty, does not authorize, or warrant the products supplied by the company, for use in a system that may affect life or personal safety or
for use as a critical component.